Compact and Lightweight design that is ideal for moving from job site to job site. It offers the most robust, high-capacity designs in the industry. It is setting the standard with intelligent operator controls, safety indication layouts, adjustable load step resolution, and lightweight designs. It is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems.
1. Function
1) User could load any power within rated power, can test stable state three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time of generating set.
2) Whether load/unload by manual control panel, remote control or by PC software control, user can pre-set the power then press the master load button.
3) Control mode: user can choose local manual control, remote control or Intelligent control(PC control)
3.1 Local manual control: there is local control panel in load bank, with multi load steps, min load steps 1kW, controlled by buttons.
3.2 Remote control: remote controller connected the load bank with control cable.
3.3 Intelligent control: user can control load bank by data processing software of PC to make automatic load/unload, display, record and manager the test data, form curve, graph and can be printed.
4) Control mode interlock: there is switch in control panel to choose control mode, other control mode is invalid if user choose one control mode.
5) With data processing software, could form curve of current, active power, reactive power, apparent power, power factor, frequency and can be printed.
6) One-key load/unload: user can load or unload with one key easy to control.
7) 3 line LED multi-function meter display.
2. Data Processing Software Functions:
1) Communication type: through RS232, RS485 or USB interface.
2) Load mode: manual load or automatic load.
3) Manual load: input power and power factor.
4) Automatic load: User can set several periods of power and time, and in turn of 0%→25%→50%→75%→100%, etc preset order to make automatic load testing.
5) Parallel testing: when several load banks parallel working, parameters of each load bank can be displayed and recorded, so do the final parameters of paralleling working.
6) Real-time parameter: Current, voltage, power, power factor, frequency, time, etc could be displayed by software.
7) Safety monitoring: User can know the working conditions of load bank through software indicating light. When in abnormal stop protection, software will indicate the reasons of stopping.
8) Data collection interval: the min saving interval is 2 seconds.
9) Data saving and in query: testing data could be saved in software, user can query at any time.
10) Data display: it could display real-time data and history data; user can print voltage, current, frequency, power graphs and charts.
11) Charts and graphs are output in format of JPG while testing data output in Excel format, and all can be printed.
3. Protection
1) User can press the emergency stop button in the panel to unload immediately when the load bank is abnormal while working.
2) Over-load: Automatic load dump and give alarm when voltage is over safety thresholds.
3) Over-heat protection: Automatic load dump and give alarm when temperature is over safety thresholds.
4) Short Circuit Protection: Fuse could avoids damage to equipment when short circuit or current overload.
4) Fan protection: Machine could not do load testing before working power of fan is on.
5) The machine will unload and give alarm when any fan is abnormal or with insufficient air volume, etc.
6) When control power cable in wrong connections, 3 phase fans can also work in good conditions.
7) Protection button: there are some protection buttons can be switched off when false alarm or for special requirements.
4. Technical Parameter
System Parameter |
Rating voltage/frequency |
415VAC, 3 phase 3 wire 50HZ When voltage lower than 415V, it will change according to Ohm' law |
Max Load Power |
Resistive Load: 1000kW |
Load Resolution |
Resistive Load: 13 steps, 1kW,2KW,2kW,5kW,10kW,10kW,20kW,50kW,100kW, 200kW,200kW, 200kW,200kW |
Power Factor |
1 |
Load Tolerance (each step) |
±5% |
Load Tolerance (overall) |
±3% |
Fan &Control Voltage |
External 415V 3 phase 4 wire 50HZ |
Wire Connection |
Load bank input--Copper bar (star coupling "Y") Connect to 5 pcs of 1X240sqm single core cable per phase, total 15pcs Control power input--Connector-bar |
Communication Interface |
RS485,RS232 |
Insulation |
F |
Max Protection Grade |
IP55 |
Duty Cycle |
Continuous |
Cooling |
Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling |
Enclosure |
Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Internal Lighting |
Adequate internal lighting will be provided |
Transportation |
Hoisting, there are lifting lug in top of casing |
Color |
Grey RAL7035 or as required |
Dimensions |
About 3000mm*2350mm*2591mm(L×W×H) |
Operating Environment Parameter |
Ambient Temperature |
-10ºC~+55ºC |
Relative Humidity |
≤95% |
Atmospheric Pressure |
86~106kPa |
Brands of Main Components |
Contactor |
Schneider |
Fuse |
Miro |
ACB 1600A |
Schneider |
PLC |
Siemens |
Alloy Resistor |
(self-developing) |
Data Processing Software |
(self-developing) |