• 500kw Resistive Load Bank for Generator Load Test
  • 500kw Resistive Load Bank for Generator Load Test
  • 500kw Resistive Load Bank for Generator Load Test
  • 500kw Resistive Load Bank for Generator Load Test
  • 500kw Resistive Load Bank for Generator Load Test
  • 500kw Resistive Load Bank for Generator Load Test

500kw Resistive Load Bank for Generator Load Test

Conditions
of Use:
Land Use
Usage: Common Units
Output Type: AC Three Phase
Cooling
Method:
Air Cooled
Installation
Method:
Portable
Generator
Type:
Diesel Generator
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AC400-500kw
Name
Load Bank
Voltage
380V, 400V, 415V, 440, 600V etc
Power
500kw
PF
1
Frequency
50Hz, 60Hz
Resistor
Metal Alloy
Transport Package
Wooden Case
Specification
ISO
Trademark
triumph load
Origin
China
HS Code
9030339000
Production Capacity
1000units

Product Description

Function of 1KW to 500KW 3 ph genset Load Bank 

1)      User could load any power within rated power, can test stable state three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time of generating set.

2)      Whether load/unload by manual control panel, remote control or by PC software control, user can pre-set the power then press the master load button.
500kw Resistive Load Bank for Generator Load Test500kw Resistive Load Bank for Generator Load Test500kw Resistive Load Bank for Generator Load Test

3)      Control mode: user can choose local manual control, remote control or Intelligent control(PC control)

3.1 Local manual control: there is local control panel in load bank, with multi load steps, min load steps 1kW, controlled by buttons.

3.2 Remote control: remote controller connected the load bank with control cable.(optional)

3.3 Intelligent control: user can control load bank by data processing software of PC to make automatic load/unload, display, record and manager the test data, form curve, graph and can be printed.

4)      Control mode interlock: there is switch in control panel to choose control mode, other control mode is invalid if user choose one control mode.

5)      With data processing software, could form curve of current, active power, reactive power, apparent power, power factor, frequency and can be printed.

6)      One-key load/unload: user can load or unload with one key easy to control.

7)      3 line LED multi-function meter display.

Protection of 1KW to 500KW 3 ph genset Load Bank 

1) User can press the emergency stop button in the panel to unload immediately when the load bank is abnormal while working.

2) Over-load: Automatic load dump and give alarm when voltage is over safety thresholds.

3) Over-heat protection: Automatic load dump and give alarm when temperature is over safety thresholds.

4) Short Circuit Protection: Fuse could avoids damage to equipment when short circuit or current overload.

4) Fan protection: Machine could not do load testing before working power of fan is on.

5) The machine will unload and give alarm when any fan is abnormal or with insufficient air volume, etc.

6) When control power cable in wrong connections, 3 phase fans can also work in good conditions.

7) Protection button: there are some protection buttons can be switched off when false alarm or for special requirements. 

Technical Parameter of 1KW to 500KW 3 ph genset Load Bank 

AC400-500kW Automatic Load Bank

Rating Voltage/Frequency

400VAC/50Hz, 3 phase 4 line, line voltage 400V, phase voltage 230V

Rated Load Power

Resistive load: 500kW

Installed Capacity

Resistive load: 500kW

Load Step

1,2,2,5,10,10,20,50,100,100,200kW, min step load: 1kW

PF(Power Factor)

1

Load Tolerance  (each step)

±5%

Load Tolerance(overall)

±3%

Display Precision

0.5 class

Control Power

380VAC/50Hz, 3 phase 4 line, 220V 1-phase

Wire Connection

Load power supply input--Copper bar (star coupling)

Control power supply input--Connector-bar

Insulation

F

Duty Cycle

Continuous  

Cooling Type

Force air cooling, horizontal air inlet and horizontal air outlet

Transportation

Hoisting, there are lifting lug on top and castors at the bottom of casing

Casing Color

Grey(RAL7035)or as required

Operating Environment Parameter

Workplace

Indoor

Ambient Temperature

-10ºC~+50ºC

Relative Humidity

≤95%

Altitude

≤2500 meter

Atmospheric Pressure

86~106kPa

Brands of Main Components

Contactor

Schneider

Fuse

DELIXI

MCU

INFINEON

Data processing software

Kaixiang(self-developed)

Alloy Resistance

Kaixiang(self-developed)


500kw Resistive Load Bank for Generator Load Test
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now