• AC 500kw Resistive Load Bank to Test Generator
  • AC 500kw Resistive Load Bank to Test Generator
  • AC 500kw Resistive Load Bank to Test Generator
  • AC 500kw Resistive Load Bank to Test Generator
  • AC 500kw Resistive Load Bank to Test Generator
  • AC 500kw Resistive Load Bank to Test Generator

AC 500kw Resistive Load Bank to Test Generator

Conditions
of Use:
Trailer Type, Marine, Land Use
Usage: Standby Unit
Output Type: AC Three Phase
Cooling
Method:
Air Cooled
Installation
Method:
Portable
Generator
Type:
Diesel Generator
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AC400-500KW
Voltage
380V,400V,415V,440V,690V
Power
500kw
Frequency
50Hz, 60Hz
PF
1
Cooling
Air Cooled
Resistor
Metal Alloy
Color
Ral 7035
Warranty
12 Months
Transport Package
Wooden Case
Specification
ISO
Trademark
Triumph Load
Origin
China
HS Code
903033900
Production Capacity
800 Sets Per Year

Product Description


Product Introduction:
Resistance/inductance/capacity Automatic load bank
Automatic AC load bank main used to test the capability and aging degree for high-power ups on-line, inverter, switch power and diesel generator set for electric power, telecom department and manufacturer. It can ensure the reliability of constant power charge that adopts uniformly stepped power input, energy consumption work model and forced air-cooling model. It is of high power density, no red hot phenomenon and automatic protection function overheated. It can't be overheated and broken when the fans stop working. The complete machine can be operated simply and maintain convenient that adopts module design. It can test voltage and current according to client's request, and provide scientific test measures for high-power AC equipment.
AC 500kw Resistive Load Bank to Test Generator
 
Main functions
1. Users can set adjustable discharge power according to capability parameter and test request.
2. Discharge time can be set: load can be closed time out.
3. Voltage and current value can be displayed with digital meter.
4. The complete machine is of resistance breaking automatic overheated adopts new power consumption component.
5. AC load bank is of all kinds of specifications and series, and include resistance, inductive and capacitive load.
6.  It 's of machine combination function.

Rating Voltage/Frequency

400VAC,50Hz/60Hz

Compatible voltag/Frequency

Resistive Load: 500kW

Load Step

Resistive Load:11 steps:1, 2, 2, 5, 10, 10, 20, 50, 100, 100, 200kW

Power Factor

1.0

Load Tolerance(each step)

±5%

Load Tolerance(overall)

±3%

Display Precision

0.5 class

Control Power Supply
380VAC/50Hz , 3phase

Wire Connection
3phase+N

Communication Interface

RS485, RS232

Duty Cycle
Continuous

Cooling
air cooled, vertical air exhaust

Transportation

Hoisting, there are lifting lug in top of casing and casters in bottom of load bank

Dimension

About 1550 mm×1250mm×1680mm(Length *Width*Height)

Weight

About 600kgs 

Ambient Temperature

-10ºC~+50ºC  (14°F~122°F)

Relative Humidity

≤95%

Altitude

≤2500 meters

Atmospheric Pressure

86~106kPa

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now