Basic Info.

Model NO.
AC11-4000kw
Voltage
11kv
Power
4MW
Frequency
50Hz,60Hz
PF
1
IP
54
Control
Local and Remote
Communication
RS485, RS232
Container
20FT
Warranty
12 Months
Transport Package
Container
Specification
ISO
Trademark
Triumph Load
Origin
China
HS Code
903033900
Production Capacity
300units

Product Description

System Parameters
Rated voltage/current AC 3 phase 3 wire11KV/50Hz
Max load power Resistive load:4000kW
Load steps Resistive load(R):500kw,500kw,500kw,500kw,1MW,1MW
Power factor 1
Load tolerance(each step) ±5%
Load tolerance(overall) ±3%
Display precision Class 0.5
Control Power Supply 380VAC, 3 phase 4 wire ,50Hz
Control mode Local manual control: use control panel to control(used for maintenance)
Remote manual control: use remote controller to control.
Remote intelligent control: use data management software on PC to control.
Wiring method Load power supply input--cooper bar(star connection)
Control power supply input--connector bar
Communication interface RS485,RS232
Insulation class Class F
Protection grade  IP54 during storage state. Power bin IP21, other IP55 during operation
Duty cycle Continuous
Cooling type Forced air cooling, horizontal air inlet, vertical air outlet.
Enclosure structure Container sealing, with ladder to top of enclosure, with air inlet and air outlet mesh and protection door.
Transportation Hoisting, with lifting lugs on top and standard installation fixing hole at bottom
Internal Lighting Adequate internal lighting
Alarm light(red) Built in alarm light  
Enclosure color Grey(RAL7035)
Enclosure dimension About 9058 mmx2438 mm×2591mm(L×W×H)