1200kw Resistive Load Bank for Diesel Generator Testing

Conditions
of Use:
Land Use
Usage: Common Units
Output Type: AC Three Phase
Cooling
Method:
Air Cooled
Installation
Method:
Portable
Generator
Type:
Testing Quipment
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
Resistive Load bank 1200KW
Voltage
AC600V
Frequency
50/60Hz
Max Load Power
1200kw
Power Factor
1
Load Tolerance(Each Step)
±5%
Load Tolerance(Overall)
±3%
Display Precision
0.5 Class
Dimension
2500*2000*2000mm
Weight
1500kg
Insulation Grade
F Class
Transport Package
Container
Specification
1200kw
Trademark
triumph load
Origin
China
HS Code
9030339000
Production Capacity
10000set/Year

Product Description

1200kw Resistive Load bank for Diesel Generator Testing
1.Product Introduction
1200KW Resistive Loadbank For Diesel Generator Testing
It is designed for AC power maintenance,could be used widely in communication base,power supply,power station etc.This machine is small,light weight digital table display,easy operation,high intelligence, set the parameters 
of constant current discharge process can be done automatically.
2.1200KW Resistive Loadbank For Diesel Generator Testing Working Environment
Altitute:≤2500m
Temperature:-10°C~50°C
Humidity:≤95%RH
Working Mode:Continuous work(>6hours continuous long-term work per day)
 3.1200KW Resistive Loadbank For Diesel Generator Testing Technical Specifications

Technical parameter

AC600-1200kW

Rated voltage /Frequency

3 Phase 4 Wire AC 600V/50Hz

Max load power

Resistive load: 1000kW

Load step

Resistive load: 14steps; 1, 2, 2, 5, 10, 10, 20, 50, 100, 200, 200, 200, 200, 200kW

Power factor

1

Load Tolerance(each step)

±5%

Load Tolerance(overall)

±3%

Display Precision

0.5 class

Control Power Supply

External AC380V/50Hz  3 phase 4 wire

Wire Connection

Load Power Supply Input--Copper bar (star connection)
Control power supply input--Connector bar

Insulation grade

F class

Duty cycle

Continuous

Cooling

Forced air cooling, Horizontal inlet air, Upward cooling

Transportation

Hoisting, there are lifting lug in top of casing and casters in bottom of load bank

Casing Color

Grey(RAL7035)

Dimension

About 2500 mm*2000mm*2000mm(length*width*height)

Weight

About 1500kg

Operating Environment Parameter

Ambient Temperature

-10ºC~+50ºC

Relative Humidity

≤95%

Altitude

≤2500 meters

Atmospheric Pressure

86~106kPa

Main components brand

Contactor

Schneider

Circuit Breaker

Siemens

Fuse

Delixi

SCM

Infineon

Alloy Resistor

Kaixiang

Data Management Software

Kaixiang
1200kw Resistive Load Bank for Diesel Generator Testing
1200kw Resistive Load Bank for Diesel Generator Testing


4.Why choosing us

The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
The most patent technology and scientific research awards gainer in China.
Advanced detection method and strict inspection procedure build the qualified quality.
Customized production meet the individual requirement.
Prompt delivery & excellent after sales service.
Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.
5.Contact Information


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now