Basic Info.

Model NO.
AC Load Bank 600kw
Max Load Power
600kw
Power Factor
1
Load Tolerance(Each Step)
±5%
Load Tolerance(Overall)
±3%
Display Precision
0.5 Class
Dimension
1800mm*1420mm*1190mm
Weight
800kg
Insulation Grade
F Class
Transport Package
Wooden Case
Specification
5cbm
Trademark
Triumph Load
Origin
Hebei, China
HS Code
9030339000
Production Capacity
1000sets/Year

Product Description

Outdoor AC Load Bank 600kw load banks for generator UPS testing
1.Product Introduction

Intelligent Resistive 600KW Load Bank for Generator Testing
1.Bigger and higher Power Load: parallel running  to finish super power testing, and   realize much bigger       power loading.
2.Accurate Data: with high precision data collection module and measuring meter, related 
  equipment has passed the many certifications.
3.Control Mode:  local panel operation, remote box controlling, and intelligent software.
4.Intelligent Loading: after setting generator rated power in software, system realize 
  rapid loading through preset proportion, automatically and continuously load multiple 
  power value and common tests, like stepping, full load, and over load, so that improve 
  working efficiency.
5.High Efficiency Data Management: display real-time testing data, generate curves graphs   automatically,also can export data into excel or word. 
6.Protection Function: multiple protection, like over temperature, over voltage,
  Short Circuit and Insulation Protection,Fan Interlock protection,Emergency Stop, Alarm   protection

It is designed for AC power maintenance,could be used widely in communication base,power supply,power 
station etc.This machine is small,light weight digital table display,easy operation,high intelligence, set the 
parameters of constant current discharge process can be done automatically.
Outdoor AC Load Bank 600kw Load Banks for Generator UPS TestingOutdoor AC Load Bank 600kw Load Banks for Generator UPS Testing
2.Intelligent Resistive 600KW Load Bank for Generator Testing Working Environment
Altitute:≤2500m
Temperature:-10°C~50°C
Humidity:≤95%RH
Working Mode:Continuous work(>6hours continuous long-term work per day)
 3.Intelligent Resistive 600KW Load Bank for Generator Testing Technical Specifications
Technical Parameters
Rating Voltage/Frequency AC 380V/50Hz, 3 phase 4 Line
Max Load Power Resistive Load: 600kW
Load Step Resistive Load:11 steps; 1,2,2,5,10,10,20,50,100,200,200kW
Power Factor 1
Load Tolerance(each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Control Power Supply External 380VAC, 3phase 4wire 50Hz,
Wire Connection Load Power Supply Input--Copper bar (star connection)
Control power supply input--connector bar
Communication Interface RS485, RS232
Insulation Class F
Working Mode Continuous Working
Cooling Forced air cooling,Horizontal air inlet,Horizontal air outlet
Transportation Hoisting, there are lifting lug in top of case and wheel castors in bottom
Color Orange(RAL2008)
Dimension Approximately; 1800mm*1420mm*1190mm
(Width *Length *Height)
Operating Environment Parameter
Ambient Temperature -20ºC~+50ºC
Relative Humidity ≤95%
Altitude ≤2500 meters
Atmospheric Pressure 86~106kPa

Outdoor AC Load Bank 600kw Load Banks for Generator UPS Testing
Outdoor AC Load Bank 600kw Load Banks for Generator UPS Testing



4.Why choosing us
The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
The most patent technology and scientific research awards gainer in China.
Advanced detection method and strict inspection procedure build the qualified quality.
Customized production meet the individual requirement.
Prompt delivery & excellent after sales service.
Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.




 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now