Thank you for using AC415-1000kW Automatic Load Bank. The system accurately test output power and load capacity of all kinds of generators, main electrical parameters including the dynamic parameters tested.
Technical Parameters |
|
Rating Voltage/Frequency |
440VAC 3 phase 4 wire 50Hz, phase voltage 250V |
Max Load Power |
Resistive Load: 1000kW |
Load Step (400V/50Hz) |
Resistive Load:10steps; 1,2,2,5,10,10,20,50,50,100,200,500kW. Reactive Load steps:1,2,2,5,10,10,20,50,50,100,200,500kvar Remarks: When input voltage less than rated voltage, the power of the power buttons will decrease according to Ohm's Law. |
Power Factor |
1 |
Load Tolerance (each step) |
±5% |
Load Tolerance (overall) |
±3% |
Display Precision |
0.5 class |
Control Power Supply |
External power supply 415VAC 3 phase 4 wire 50hz |
Wire Connection |
Load Power Supply Input--busbar (star connection) Control power supply input--terminal block |
Communication Interface |
RS485, RS232 |
Insulation Class |
F |
Protection grade |
IP54 during storage state. Power bin IP21 |
Working Mode |
Continuous Working |
Cooling |
Forced air cooling |
Transportation |
Lifting, there are load-bearing rings on the top of the chassis and foot wheels at the bottom. Add a handle on the front and a handle on the back of the equipment to facilitate daily procrastination. |
Control Panel |
Control panel with transparent windows. Load bank have electric indication, fan operation instructions, etc. |
Identify |
All the places involved in the identify include device body, control panel, software theme bar, instruction manual, etc that change the original identify with customer identity EPD. The identify style is shown on the last page of the technical agreement. |
Chassis color |
Gray(RAL7035) |
Dimension |
Approximately 1600mm×1250mm×1500mm (Width *Length *Height) |
Weight |
About 600kg. |
Operating Environment Parameter |
|
Using Place |
Outdoor |
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Altitude |
≤1500 meters |
Atmospheric Pressure |
86~106kPa |
--Load testing: Load power that not beyond the rated power, testing and display stable state 3 phases voltage, current, active power, frequency, working time, etc of generator sets.
--Load/unload with one key: Whether manual control, remote control or software control, user can preset the power, then press load master button. Load bank loaded according to preset power to avoid load fluctuation during the power changing.
--Control Pattern: user can choose local control and intelligent control.
--Local Control: There is local control panel with several power steps; user can load/unload by button.
--Intelligent Control: Through data processing software in PC, user can make automatic load, display, record and manage the testing data, form curves, tables, also print is available.
--Control Pattern interlock: There is control pattern switch, when choose one control pattern, operation of other pattern is invalid, avoid the clash.
--Local meter display data: Local meter can display 3 phases voltage, current, active power, frequency and so on.
--Communication pattern: Intelligent control use photoelectric isolated RS485 interface connect to PC, with great anti-interference performance to make system control stable. Also user can use USB or RS232 through converter.
--Load pattern: Manual Load or Automatic Load.
--Manual Load: Input power, system will load according to preset power.
--Automatic load: User can preset power and length of working time of several load periods, as per 0%→25%→50%→75%→100% or 110% to make testing.
--Real-time parameter: Through software to display voltage, current, power, power factor, frequency and time, etc.
--Data Collection Interval: the minimum data resolving time is 2s.
--Security monitoring and control: Monitor working state of the load bank by watching software light, when abnormally stop and protect, it can show the reason.
--Data save and query: All the test data is saved in the software, easy to query in the history testing data.
--Graphical display: Show real-time or history testing data, and support to print curve and graph as follows:
1) Graphs of real-time voltage, current, frequency and power; 2) Voltage graph
3) Current graph; 4) Power graph; 5) Frequency graph; 6) Power factor graph
--Data format: all the curves and graphs can be outputted as".doc"format, testing data can be outputted as ".xls" format, and can be printed.
--Emergency Stop: You can press the Emergency Stop switch in the panel, when the load bank is locked in this state, it cannot add any load.
--Overvoltage Protection: When input voltage is over the safe value, it can unload automatically and give an alarm.
--Short circuit Protection: When short circuit, fuses in the load bank can insure to unload automatically.
--Overheating Protection: When temperature is over the safe value, it can unload automatically and give an alarm.
--Fan interlock Protection: Load bank cannot add any load when working power of fan is off.
--Protection Buttons: There are buttons for some protection, when misinformation occurs or user has special needs, user can temporarily turn off the corresponding protection function.
--Chassis Ground Protection: In order to avoid the danger of electric shock when operating, the load bank is equipped with special ground protection terminal.
Why choosing us
The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
The most patent technology and scientific research awards gainer in China.
Advanced detection method and strict inspection procedure build the qualified quality.
Customized production meet the individual requirement.
Prompt delivery & excellent after sales service.
Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.