Testing Equipment (Load Bank) 550kw Load Bank Maintenance

Voltage: AC 400V/50Hz, 3 Phase 4 Wire
Max Load Power: 550kw
Power Factor: 1
Load Tolerance(Each Step): ±5%
Load Tolerance(Overall): ±3%
Display Precision: 0.5 Class
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
550kw load bank maintenance
Weight
900kg
Insulation Grade
F Class
Cooling
Forced Air Cooling, Horizontal Inlet Air, Upward C
Transport Package
Wooden Case
Specification
1460*1980*1800mm
Trademark
Triumph Load
Origin
Hebei, China
HS Code
9030390000
Production Capacity
1000sets/Year

Product Description

Testing Equipment (Load Bank) 550kw load bank maintenance

1. Product Introduction

AC Generator Testing Equipment (Load Bank) 550kW

It is designed for AC power maintenance,could be used widely in communication base,power supply,power station etc.

This machine is small,light weight digital table display,easy operation,high intelligence, set the parameters of constant 

current discharge process can be done automatically.

 

2. AC Generator Testing Equipment (Load Bank) 550kW Working Environment

Altitute:≤2500m

Temperature:-10°C~50°C

Humidity:≤95%RH

Working Mode:Continuous work(>6hours continuous long-term work per day)

 

3. AC Generator Testing Equipment (Load Bank) 550kW Technical Specifications

Technical parameter

AC400-550kW

Rated voltage /Frequency

AC 400V/50Hz,3 Phase 4 Wire

Max load power

Resistive load: 560kW

Load step

Resistive load: 12 steps, 1, 2, 2, 5, 10, 20, 20, 50, 50, 100, 100, 200kW.

Power factor

1

Load Tolerance(each step)

±5%

Load Tolerance(overall)

±3%

Display Precision

0.5 class

Control Power Supply

External AC380V/50Hz  3 phase 4 wire

Wire Connection

Load power supply input--Copper bar (star coupling)

Control power supply input--Amphenol connector

Insulation grade

F class

Duty cycle

Continuous

Cooling

Forced air cooling, Horizontal inlet air, Upward cooling

Transportation

Hoisting, there are lifting lug in top of casing and casters in bottom of load bank

Casing Color

Grey(RAL7035)

Dimension

About 1460 mm*1980mm*1800mm(length*width*height)

Weight

About 900kg

Operating Environment Parameter

Ambient Temperature

-10ºC~+50ºC

Relative Humidity

≤95%

Altitude

≤2500 meters

Atmospheric Pressure

86~106kPa

Main components brand

Contactor

Schneider

Circuit Breaker

Siemens

Fuse

Delixi

SCM

Infineen

Alloy Resistor

Kaixiang

Data Management Software

Kaixiang

 

4. AC Generator Testing Equipment (Load Bank) 550kW Overall Appearance
Testing Equipment (Load Bank) 550kw Load Bank Maintenance


  

Testing Equipment (Load Bank) 550kw Load Bank Maintenance
Testing Equipment (Load Bank) 550kw Load Bank Maintenance


5. More Pictures of AC Load Bank
Testing Equipment (Load Bank) 550kw Load Bank Maintenance
Testing Equipment (Load Bank) 550kw Load Bank Maintenance

6. Why choosing us

  1. The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
  2. The most patent technology and scientific research awards gainer in China.
  3. Advanced detection method and strict inspection procedure build the qualified quality.
  4. Customized production meet the individual requirement.
  5. Prompt delivery & excellent after sales service.
  6. Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
  7. Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
  8. Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.

7. Contact Information


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.