13.8kv 2MW Resistive Load Bank for Gas Turbine Testing

Rated Voltage: 11kv 3phase 50Hz/60Hz
Load Wire Connection: 3phase 3wire
Power Factor: 1
Cooling: Forced Air Cooling
Control Mode: Manual or Software
Rated Power: 4MW
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AC/DC Load Bank
Dimension
9150*2350*2591mm
Transport Package
Inner: Plastic Film Wrapped Outside: Wooden Case
Specification
ISO9001: 2008
Trademark
Triumph load
Origin
Shijiazhuang, Hebei, China
HS Code
9030390000
Production Capacity
20 Sets/Month

Product Description

2.1 Measuring Function
Steady-state Test: load power in rated range, measure generator steady-state 3 phase voltage, current, active power, reactive power, apparent power, power factor, frequency, and running time.
2.2 Dummy Load Function

  1. Working principle and pattern: Dynamic adjustment principle, when real load is no more than X% (XkW) output power of DG set, load bank will automatically add load in 5 seconds to make sure real load power + load bank power ≥XkW  and remove all load power in 5 seconds when real load power no less than XkW.
  2. 3 line LED multi-function meter can display real-time voltage and current of three phase and each phase, resistive power, power factor, apparent power, frequency and running time of generating set.
  3. User can pre-set the power then press the master load button.
  4. Control mode: Automatically load/unload.
  5. Through RS485 connect PC and load bank, the real-time data can be transferred to PC, use data management software, data can be formed into curves, exported to EXCEL or JPG file.

2.2 Control Mode
(1) Control Mode: local, remote or intelligent control(software) for choosing.
(2) Local Control: local control panel with several power steps, load or unload by switch on-off and read parameter values from measuring meter.
(3) Remote Control:through the switch in the remote control box, control the load over a long distance.
(4) Intelligent Control: through data processing software, realize all the test functions, display, record and manage the testing data, and generate curves, graphs and tables can be printed.
(5) Control Mode Interlock: with control mode switch, no matter chooses which mode, operation of other mode is invalid, avoid the clash.
2.3 Intelligent Load Function
(1) Communication Mode: using photoelectric isolated RS485 communication serial port connect to PC, and with great anti-interference performance to make system control stable. Through converts like USB or RS232 realize communication protocol conversion.
(2) Load Mode: steady-state load (manual load, preset load and automatic load) and transient state load (instant load and instant unload).
(3) Manual Load: input power and power factor, and load according to the preset value.
(4) Preset Load: input generator related parameters, then choose the preset proportion from 0% 25%, 50%, 75%, 100% or other available order and calculate the power value automatically and realize rapid load.
(5) Automatic Load: set several load stages and duration, then complete the process according this stages automatically. Pause at any time or start to next stage in the load process.
(6) Parallel Test: several load banks work in parallel, the parallel test via software. Parameters of each set can be displayed in each meter and total parameter values can be displayed and recorded.
2.6 Technical Parameter

System Parameter
Rating voltage/frequency 13.8KV, 3 phase 3 wire 60Hz
Max Load Power  Resistive Load: 2MW
Load Resolution  Total 4 steps 500kW,500kW,500kW,500kW 
Power Factor 1
Load Tolerance (each step) ±5%
Load Tolerance (overall) ±3%
Fan &Control Voltage External AC 3 phase 4 wire, 380V/60Hz
Wire Connection Load bank input--Copper bar (star coupling "Y")
Control power input--Connector-bar
Communication Interface RS485,RS232
Insulation F
Max Protection Grade IP55
Duty Cycle Continuous  
Cooling Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling
Enclosure Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door
Internal Lighting Adequate internal lighting will be provided
Transportation Hoisting, there are lifting lug in top of casing
Color Grey RAL7035 or as required
Dimensions About 12192mm×2438mm×2591mm(L×W×H)
Operating Environment Parameter
Ambient Temperature -20ºC~+50ºC
Relative Humidity ≤95%
Atmospheric Pressure 86~106kPa
Brands of Main Components
Contactor Xiguang
PLC Siemens
Fuse Chuantai
Alloy Resistor (self-developing)
Data Processing Software  (self-developing)

13.8kv 2MW Resistive Load Bank for Gas Turbine Testing
13.8kv 2MW Resistive Load Bank for Gas Turbine Testing
13.8kv 2MW Resistive Load Bank for Gas Turbine Testing
13.8kv 2MW Resistive Load Bank for Gas Turbine Testing
13.8kv 2MW Resistive Load Bank for Gas Turbine Testing