Customization: | Available |
---|---|
Certification: | ISO9001, Generator Test |
Protection: | Corrosion Resistance |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
diesel generator testing load bank 500kw load bank for sale for generator ups testing
1.Product Introduction
AC415-500kW Automatic Load Bank | |
Rating Voltage/Frequency | 415VAC 3 phase 4 wire, wire phase: 415V, phase voltage: 240V /50Hz/60Hz |
Rated Load Power | Resistive load:500kW |
Installed Capacity | Resistive load: 500kW |
Load Step | 1kW,2kW,2kW,5kW,10kW,20kW,20kW,50kW,100kW,100kW,200kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | External 380VAC/50Hz/60Hz, 3 phase 4 wire |
Wire Connection | Load power supply input--Copper bar Control power supply input--Connector-bar |
Insulation | F |
Duty Cycle | Continuous |
Cooling Type | Force air cooling, horizontal air inlet and horizontal air outlet |
Transportation | Hoisting, there are lifting lug on top and castors at the bottom of casing |
Dimension | About 900mm*1100mm*1200mm(L×W×H) |
Weight | About 385kgs |
Casing Color | Grey(RAL7035)or as required |
Operating Environment Parameter | |
Workplace | Indoor or outdoor |
Ambient Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |