• 11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test
  • 11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test
  • 11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test
  • 11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test
  • 11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test
  • 11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test

11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test

Rating Voltage: 11kv, 6kv, 3pH
Rated Load Power: 5000kw
Power Factor: 1
Load Tolerance (Each Step): 5%
Load Tolerance(Overall): 3%
Insulation: F
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AC11kV-5000kW
Cooling
Forced Air Cooling
Transportation
Hoisting
Max Protection Grade
IP55
Control Power
3 Phase 4 Wire 380V/50Hz
Transport Package
Container Type
Specification
ISO9001: 2008
Trademark
triumph load
Origin
Shijiazhuang, Hebei, China
HS Code
9030390000
Production Capacity
100sets/Year

Product Description

Advantage:
The ability to test critical power systems at voltages of 1.2KV to 80kV using direct-connect, High Voltage Load Bank offers engineers flexibility, time savings, cost savings, space savings and simplicity. It mainly used to commission utility, oil & gas, and industrial power systems without the need for additional transformers and cabling.
 
Application
Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test
Eliminate the carbon deposition of generator
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment
 
11kv 6.6kV 5000KW High Voltage Load Bank For Generator Test
Rating Voltage/Frequency 11kV,6.6kV, 50/60Hz, 3 phase  
Rated Load Power Resistive load: 5000kW
Installed Capacity Resistive load: 5000kW
Load Step Resistive load: 6 steps, 500kW×2, 1000KW×4, min step load: 500KW
PF(Power Factor) 1
Load Tolerance(each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Control Power 3 phase 4 wire 380V/50Hz
Wire Connection Load power supply input--Copper bar (star coupling)
Control power supply input--Connector-bar
Communication Interface RS485, RS232
Insulation F
Max Protection Grade IP55
Way of Working Continuous Work
Cooling Forced air cooling,Horizontal inlet air,Vertical cooling
Casing Structure Container, with a ladder, air inlet and outlet with mesh enclosure and protection door
Transportation Hoisting, there are lifting lug in top of casing
Casing Color Grey(RAL7035)or as per customer's requirement
Dimension 9000 mm×2438mm×2591mm(length*width*height)
Weight About 9000kg
Operating Environment Parameter
Workplace Outdoor
Ambient Temperature -10ºC~+50ºC
Relative Humidity ≤95%
Altitude ≤2500 meter
Atmospheric Pressure 86~106kPa
Brands of Main Components
Contactor SUNGEO
Fuse CNCTCO
MCU INFINEON
Alloy Resistance Kaixiang(self-developed)
Data Processing Software Kaixiang(self-developed)

11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test
11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test
11kv 6.6kv 5000kw High Voltage Load Bank for Generator Test

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now