Customization: | Available |
---|---|
Type: | Universal Testing Machine |
Product Name: | 5500kVA Rl Inductive Load Bank |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
5500KVA RL Inductive Load Bank offers a 0.80 power factor load and is designed for testing large generators, switchgear, transformers and UPS systems. The structural skid with fork lift pockets allows for portability and is ideal for shipyards, power plants, OEMs and data centers. The RL Series is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems where rated kVA, rated power factor and rated current testing is required.
Main features and advantages
1. Control mode: (1)Local manual control panel (2)Remote manual control box (3) Remote console(include manual panel and PC control)(4)Laptop control
2. Protection function: Overvoltage, overcurrent, overheat, over low blowing rate, blower overheat, blower phase sequence reverse protection, smoke alarm etc.
3. Cooling: Industrial heavy duty blower, horizon air intake, upwards outlet, low noise.
4. Power consumption components: Made by special alloy resistance, high-temperature resisting, high heat dissipation capability, high heat stability, no naked light, safety and reliability. Running temperature is 1/3 of rating.
5. Weather-proof structure: Containerized structure provides ultra protection, protection grade higher than IP55.
6. Material and coating: The body adopt cold-rolled steel plate that processed by galvanizing corrosion protection, powder coated and spray paint.
7. Integrated & modularization design: Easy to installation, maintenance and transportation.
Technical ParameterSystem Parameter | |
Rating voltage/frequency | AC 3 phase 4 line, 400V/50Hz |
Max Load Power | Apparent Power: 5500kVA Resistive Load: 4400kW Inductive Load: 3300kvar |
Load Resolution | Resistive Load: 30 steps, 1,2,2,5,10,10,20,50,100,21*200kW Inductive Load: 25 steps, 1,2,2,5,10,10,20,50,100,100,15*200kvar |
Power Factor | 0.8 |
Load Tolerance (each step) | ±5% |
Load Tolerance (overall) | ±3% |
Fan &Control Voltage | External connection AC 3 phase 4 line, 380V/50Hz |
Wire Connection | Load bank input--Copper bar (star coupling "Y") Control power input--Connector-bar |
Communication Interface | RS485,RS232 |
Insulation | F |
Max Protection Grade | IP55 |
Duty Cycle | Continuous |
Cooling | Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling |
Enclosure | Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Internal Lighting | Adequate internal lighting will be provided |
Transportation | Hoisting, there are lifting lug in top of casing |
Color | Grey RAL7035 or as required |
Dimensions | About 9000mm*2438mm*2591mm(L×W×H) |