Customization: | Available |
---|---|
Certification: | ISO9001, Ce |
Protection: | Corrosion Resistance |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
HV Load Bank 10.5kv 2000kw Resistive Load Banks for generator testing
1.Product Introduction
10.5kV 2000kW Dry Type Dummy Load Banks
High voltage load bank,the optional voltage range is 6.6KV~35KV,can be directly used for large high voltage generator,need not to be equipped with conventional stepdown transformer.We can also provide regular load bank for high voltage equipment,need to use step-down transformer together.
2. 10.5kV 2000kW Dry Type Dummy Load Banks Application
Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection
test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test
Eliminate the carbon deposition of generator
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment
3. 10.5kV 2000kW Dry Type Dummy Load Banks Working Environment
Altitute:≤2500m
Temperature:-10°C~50°C
Humidity:≤95%RH
Working Mode:Continuous work(>6hours continuous long-term work per day)
4. 10.5kV 2000kW Dry Type Dummy Load Banks Technical Specifications
System Parameters (Single set) |
|
Rated Voltage/ Frequency |
AC10.5KV/50Hz, 3 phases 3 wire
|
Installer Capacity |
2000kW |
Step Load |
200KW, 450KW, 450KW, 450KW, 450KW, 5 steps |
Power Factor (PF) |
1 |
Load Tolerance |
5% |
Display Precision |
0.5 grade |
Control Power Supply |
AC380V/50Hz, 3 phases 5 wire |
Insulation |
F |
Max Protection Grade |
IP54 |
Working Mode |
Continuous |
Cooling |
Forced air cooling, Horizontal inlet air, Vertical cooling |
Casing Structure |
Standard 20 feet container, with a ladder to top |
Transportation |
Hoisting, there are lifting lugs in top of casing |
Dimension |
6058mm×2438 mm×2591mm |
Weight |
About 6000kg |
Working Environment Parameters |
|
Ambient Temperature |
-20ºC~+55ºC |
Relative Humidity |
≤95% |
Altitude |
≤2500 meters |
Atmospheric Pressure |
86~106kPa |
Working Temperature |
Temperature inside container: less than 35ºC,forced-air cooling |
5. 10.5kV 2000kW Dry Type Dummy Load Banks Overall Appearance