Resistive and Inductive Load Bank 4000kVA AC Load Banks for Generator UPS Testing
1.Product Introduction
AC 400V Resistive and Inductive Combined Loadbank 4000kVAHigh Power Dry Type Load Bank is composed of outdoor resistive and inductive combined load bank,data collection system,electric control module,thermal module,control part etc.It can accurately detect Marine generator output power and load capacity,and assist shipyard in acceptance of vessel,mooring test,sea trial,load test,static voltage characteristic test, speed characteristic test,overload protection test,reverse power and reverse current protection test,and parallel operation test etc.
2. AC 400V Resistive and Inductive Combined Loadbank 4000kVA System Chart
3. AC 400V Resistive and Inductive Combined Loadbank 4000kVA Working Environment
Altitute:≤2500m
Temperature:-10°C~50°C
Humidity:≤95%RH
Working Mode:Continuous work(>6hours continuous long-term work per day)
4.Resistive and Inductive Load Bank 4000kVA load banks for generator UPS testing
Technical parameter |
|
AC400-4000KVA-RL |
|
Rated voltage /Frequency |
Three-phase three-wire 400V, 50/60Hz |
Rated Capacity |
4000KVA |
Load Distribution |
When 400V/60Hz: Resistive load: 3200kW,Inductive load: 2400Kvar
|
Stepping Value |
Resistive load: 1KW Inductive load: 1Kvar |
Resistor divider file |
1KW, 2KW, 2KW, 5KW, 10KW, 20KW, 20KW, 50KW, 100KW, 200KW*15steps |
Reactance file |
1Kvar, 2Kvar, 2Kvar, 5Kvar, 10Kvar, 20Kvar, 20Kvar, 50Kvar, 100Kvar, 200Kvar*11steps |
Power factor |
0.8-1 |
Load Tolerance(each step) |
±5% |
Load Tolerance(overall) |
±3% |
Display Precision |
0.5 class |
Control Power Supply |
External AC three phase connection 380V/50Hz |
Wire Connection |
Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation grade |
F class |
Duty cycle |
Continuous |
Cooling |
Forced air cooling, Horizontal inlet air, Vertical cooling |
Transportation |
Hoisting, there are lifting lug in top of casing and casters in bottom of load bank |
Casing Color |
Grey(RAL7035) |
Dimension |
About 6058mm*2438mm*2750mm(length*width*height) |
Weight |
About 18000kg |
Operating Environment Parameter |
|
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Altitude |
≤2500 meters |
Atmospheric Pressure |
86~106kPa |
Main components brand |
|
|
|
Circuit Breaker |
Siemens |
Fuse |
Delixi |
SCM |
Infineon |
Alloy Resistor |
Kaixiang |
Data Management Software |
Kaixiang |
Testing Function
(1) Stable-state Test: load power in rated range, measure generator steady-state 3 phase voltage, current, active power, reactive power, apparent power, power factor, frequency, and running time.
(2) One-key load/unload: no mattery using software control or manual control, can set loading power first, then press master load switch, this avoid the load fluctuation.
(3) Setting Test: can catch the max and min setting value of voltage and frequency, and calculate the relative setting up and down range of voltage and frequency and adjustment rate within 100 seconds setting time.
(4) Fluctuation Test: catch the max and min fluctuating value of voltage and frequency, and calculate steady-state frequency band, steady-state voltage deviation, voltage modulation, fluctuation rate and frequency in 60 seconds fluctuation time.
(5) Transient Test (Instant Load Test): sample interval is 40μs,system catch the transient max and min value and recovery time of voltage, current, and frequency, and calculate instant load transient voltage deviation and instant load transient frequency deviation.
(6) Transient Test (Instant Unload Test): sample interval is 40μs,system catch the transient max and min value and recovery time of voltage, current and frequency, and calculate instant unload transient voltage deviation and instant unload transient frequency deviation.
(7) Harmonic Analysis: It can analysis 2~50 harmonic content and total harmonic content in voltage and current at same time.
(8) Record Wave Analysis: 5 patterns for recording voltage real-time waveform, and the record time is 4~ 280 seconds and accurately sampling at 128 points in a wave cycle at most.
5. Resistive and Inductive Load Bank 4000kVA load banks for generator UPS testing
Overall Apperance