Customization: | Available |
---|---|
Type: | Micro-Computer Control Automatic Diesel Generator |
Installation Method: | Portable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical parameter |
|
AC400-1300KVA-RL |
|
Rated voltage /Frequency |
Three-phase three-wire 400V,50Hz |
Apprent Power |
1300KVA |
Load Distribution |
When 400V: Resistive load:1040kW,Inductive load:870Kvar |
Stepping Value |
Resistive load: 1KW Inductive load: 1Kvar |
Resistor divider file |
1,2,2,5,10,10,20,40,50,100,100,100,100,100,100,100,100,100KW 18Steps |
Reactance file |
1,2,2,5,10,10,20,20,50,50,100,100,100,100,100,100,100Kvar 17Steps |
Power factor |
0.8-1 |
Load Tolerance(each step) |
±5% |
Load Tolerance(overall) |
±3% |
Display Precision |
0.5 class |
Control Power Supply |
External AC three phase connection 400V/50Hz |
Wire Connection |
Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation Grade |
F class |
Protection Grade |
IP55 |
Duty Cycle |
Continuous |
Cooling |
Forced air cooling, Horizontal inlet air, Vertical cooling |
Transportation |
Hoisting, there are lifting lug in top of casing and casters in bottom of load bank |
Casing Color |
Grey(RAL7035) |
Dimension |
4000mm*2438mm*2896mm(length*width*height) |
Weight |
About 5000KG |
Operating Environment Parameter |
|
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Altitude |
≤2500 meters |
Atmospheric Pressure |
86~106kPa |
Main components brand |
|
Contactor |
Schneider |
Circuit Breaker |
Siemens |
Fuse |
Delixi |
SCM |
Infineon |
Alloy Resistor |
Kaixiang |
Data Management Software |
Kaixiang |