Product Description
Popular used automatic AC 1000kw Resistive Load Bank for generator testing
What can the commonly used load banks test for diesel generators?
Any power within rated power 1000kw could be loaded, stable state three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time of generating set could be tested and displayed .
What is the control method?
There are three control method:manual control pannel,remote control or PC software control.And control mode interlock,other control method will be invalid if one of the load banks control method is used
What is the load mode?
1) Manual load:to input power and power factory
2) Automatic load:several periods of power and time could be set, and in turn of 0%→25%→50%→75%→100% etc preset order to make automatic load testing
Parallel testing available: when several USED load banks parallel working, parameters of each load bank can be displayed and recorded, so do the final parameters of paralleling working.
Data management including testing data collection ,data saving ,data querying ,data display( real time data and history data), data print.
LOAD STEP1,2,2,5,10,20,20,50,100,200,200,200,200kW, min step load: 1kW.
Product Parameters
Regular used AC resistive load bank parameters list as following except load banks 1000kw
AC400-1000kW Automatic Load Bank |
Rating Voltage/Frequency |
AC400V, 3 phase 4 wire, 50Hz/60Hz |
Rated Load Power |
AC400V Resistive load: 1000kW
|
Installed Capacity |
Resistive load:1010kW |
Load Step |
1,2,2,5,10,20,20,50,100,200,200,200,200kW, min step load: 1kW |
PF(Power Factor) |
1 |
Load Tolerance (each step) |
±5% |
Load Tolerance(overall) |
±3% |
Display Precision |
0.5 class |
Control Power |
External AC400V/50Hz, 3 phase 4 wire |
Wire Connection |
Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation |
F |
Duty Cycle |
Continuous |
Cooling Type |
Force air cooling, horizontal air inlet and horizontal air outlet |
Transportation |
Hoisting, there are lifting lug on top and castors at the bottom of casing with forklift hole |
Dimension |
About 1800mm*1300mm*1918mm(L×W×H) |
Weight |
About 1200kgs |
Casing Color |
Grey(RAL7035)or as required |
Operating Environment Parameter |
Workplace |
Outdoor |
Operation conditions |
When operating load banks,It need 3m-5m no obstacle away from airinlet and airoutlet, above 1 m distance between load banks |
Ambient Temperature |
-20ºC~+50ºC |
Relative Humidity |
≤95% |
Altitude |
≤2500 meter |
Atmospheric Pressure |
86~106kPa |
Brands of Main Components |
Fuse |
Miro |
PLC |
Siemens |
Data processing software |
Kaixiang(self-developed) |
Alloy Resistance |
Kaixiang(self-developed) |

Resistive load bank feature
Commonly used resistive load banks 1000kw Feature
Standard Testing Function;
High Power Load: high load power density, large capacity of single set, parallel running to finish super power testing;
Accurate Data: with high precision data collection module and measuring meter;
Flexible Control Mode:
Intelligent Loading: after setting generator rated power in software, the commonly used resistive load banks realize rapid loading through preset proportion,automatically and continuously load multiple power value and common tests, like stepping, full load, and over load, so that improve working efficiency.
High Efficiency Data Management: display real-time testing data, generate curves graphs automatically;
Comprehensive Protection Function: multiple protection, like over temperature, smoke. When in danger, AC resistive load bank automatically terminate the test and give alarm to protect safety of personnel and equipment.
Stable Running:
New Load Bank Technology: using the international advanced AC load bank technology, the resistive load banks 1000kw is able to be used when go to sea, realize Mooring Trial and Sea Trail, and simulate the real working condition of generator testing load bank running.
Mature Manufacturing Technology: load elements anti-corrosion materials; waterproof insulation container packaging,suitable for adverse environment such as ocean. Internal layout is reasonable, air channel is clear, rapid heat emission, and satisfy continuous working need.
Certifications
Resistive load banks certification ,CE certified
Company Profile
As one of the leader load banks factory ,the following load bank workshop for you better knowing us

Load bank project case
This resistive load banks are usually used for generator testing ,data center ,UPS and industrial battery testing

Hebei Kaixiang Technology was established in 1994, long-term focus on smart power detection technology
development and application in shipbuilding, petroleum, offshore platforms, data centers, communications,
power, aviation, research institutes and other areas, and in strict accordance with the ISO9001
international quality standard management system for the design, manufacture and service.
The company's core technologies are independent research, has seven patents, 10 software copyrights, two
corporate standards.Among them, Kaixiang "smart power marine generators AC load," Science and Technology
Department of Hebei Province has been named the international advanced level scientific and technological
achievements, the enterprise standard "dry AC load" to upgrade the industry standard by the Ministry of publicity.
4.Why choosing us
The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
The most patent technology and scientific research awards gainer in China.
Advanced detection method and strict inspection procedure build the qualified quality.
Customized production meet the individual requirement.
Prompt delivery & excellent after sales service.
Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.
5.Series Products:
Automatic AC load banks Intelligent AC load banks High-power load banks
Genset intelligent testing systems AC/DC load banks
Intelligent battery discharger UPS intelligent high-voltage discharger
Single cell test & discharge series DC automatic load banks
Intelligent charge/discharge tester Intelligent battery integrated tester
Intelligent battery activation series Fully automatic charger
I