• 500kw 415V Resistive Load Bank Outdoor
  • 500kw 415V Resistive Load Bank Outdoor
  • 500kw 415V Resistive Load Bank Outdoor
  • 500kw 415V Resistive Load Bank Outdoor
  • 500kw 415V Resistive Load Bank Outdoor

500kw 415V Resistive Load Bank Outdoor

Type: Universal Testing Machine
Maxcapacity: >1000KN
Accuracy Grade: 0.5
Load Way: Electronic Load
Loading Method: Dynamic Load
Display: Digital
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
pf Variable Load Bank
Control
Computer Control
Weight
500-1000Kg
Power Source
AC380V
Oil Cylinder Position
Top
Rated Power
500kw
Rated Voltage
415V, 3 Phase 4 Wire
Power Factor
1
Duty Cycle
Continuous
Cooling
Industrial Heavy Duty Blower, Horizon Air Intake
Control Mode
Manual/Remote/Software
Casing Structure
with Lifting Lugs on The Top and Castors at The Bo
Resistance
Special Alloy Resistance
Casing Material
Corrosion Resistant Aluminum Alloy
Monitoring & Display Meter
Voltage, Current, Power, Power Factor, Frequency
Transport Package
Wooden Case
Specification
ISO9001: 2008
Trademark
Triumph Load
Origin
Shijiazhaung, Hebei, China
HS Code
9030390000
Production Capacity
12 Sets/Month

Product Description

Compact and Lightweight design that is ideal for moving from job site to job site or within your facility. 
Introduction:
It offers the most robust, high-capacity designs in the industry.  It is setting the standard with intelligent operator controls, safety indication layouts, adjustable load step resolution, and lightweight designs.  It is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems. 
Main features 
1. Multiple control mode: (1) manual panel control (2) remote control (3)software control
2. Multiple display function: voltage, current, frequency, power factor, active power, reactive power, apparent power etc.  
3. Multiple protection function: overvoltage, overcurrent, overheat, over low blowing rate, blower overheat, blower phase sequence reverse protection, smoke alarm etc.
4. Forced air cooling: industrial heavy duty fan, horizon air intake, upwards outlet, low noise.
5. Power consumption components: made by special alloy resistance, high temperature resisting, high heat dissipation capability, high heat stability, no naked light, safety and reliability. Running temperature is 1/3 of rating. 
6. Weather-proof structure: containerized structure provides ultra protection, protection grade higher than IP55.
7. Material and coating: the body adopt cold-rolled steel plate that processed by galvanizing corrosion protection, powder coated and spray paint.
8. Integrated & modularization design: compact structure, easy to installation, maintenance and transportation.
9. Software control: it can test and display voltage, current, frequency, power factor, active power, reactive power, apparent power etc, the test result can be store & print and form all kinds of curve, chart and test report.

Technical Paramters
AC415-500kW Automatic Load Bank
Rating Voltage/Frequency 415VAC, 3 phase 4wire 50HZ
Rated Load Power 510kW
Load Step 1,2,2,5,10,20,20,50,100,100,200kW, min step load: 1kW
PF(Power Factor) 1
Load Tolerance  (each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Fan & Control Power External 415VAC, 3 phase 4wire 50HZ  
Wire Connection Load power supply input--Copper bar (star coupling)
Control power supply input--Connector-bar
Insulation F
Duty Cycle Continuous  
Cooling Type Force air cooling, horizontal air inlet & air outlet, with louver and protection door
Transportation Hoisting, there are lifting lug on top
Dimension About 1800mm*1300*1070mm(L×W×H)
Weight About 700kgs
Enclosure Color  As required
Operating Environment Parameter
Workplace Outdoor
Ambient Temperature -20ºC~+50ºC
Relative Humidity ≤95%
Altitude ≤2500 meter
Atmospheric Pressure 86~106kPa
Brands of Main Components
Contactor Schneider
Fuse Miro
PLC Siemens
Data processing software Kaixiang(self-developed)
Alloy Resistance Kaixiang(self-developed)

The Main Application Of The Load Bank 
Factory testing of engines generator sets
To reduce "wet stacking" problems
Periodic exercising of stand-by engine generator sets
Load testing of AC power source
On-site acceptance testing
UPS system testing and maintenance
New projects inspection and battery system maintenance
Load optimization in prime power applications