• 500kw Resistive Dummy Load Bank
  • 500kw Resistive Dummy Load Bank
  • 500kw Resistive Dummy Load Bank
  • 500kw Resistive Dummy Load Bank
  • 500kw Resistive Dummy Load Bank

500kw Resistive Dummy Load Bank

Rated Power: 500kw
Rated Voltage: 400V 3phase 50Hz/60Hz
Load Steps: 1, 2, 5, 10, 20, 50, 100, 200kw
Duty Cycle: Continuous
Cooling Type: Forced Air Cooling
PLC: Siemens
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AC400-500kW
Contactor
Imported Brand
Dimension
1540mm*1250mm*1680mm
Trademark
Triumph Load
Origin
China
HS Code
9030339000
Production Capacity
10 Units/Month

Product Description

500KW Load Bank for 3 Phase Generator Test

Load input voltage: AC400V, 3phase 4 wire, 50HZ, Rated power: 500KW. Power factor: 1 Load steps: 1kw 2 kw 2 kw 5kw 10kw 10kw 20kw 50kw 100kw 100kw 200kw  min load: 1kw

AC415V-500kW Resistive Load Bank
Rating Voltage/Frequency 415VAC, 3 phase 4wire 50Hz/60Hz
Rated Load Power 500kW
Load Step 1,2,2,5,10,10,20,50,100,100,200kW, min step load: 1kW
PF(Power Factor) 1
Load Tolerance  (each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Fan & Control Power External 415VAC, 3 phase 4wire 50Hz  
Wire Connection Load power supply input--Copper bar (star coupling)
Control power supply input--Connector-bar
Insulation F
Duty Cycle Continuous  
Cooling Type Force air cooling, horizontal air inlet & air outlet, with louver and protection door
Transportation Hoisting, there are lifting lug on top
Protection IP55
Dimension About 1800mm*1300*1070mm(L×W×H)
Weight About 700kgs
Enclosure Color  As required
Operating Environment Parameter
Workplace Outdoor
Ambient Temperature -20ºC~+50ºC
Relative Humidity ≤95%
Altitude ≤2500 meter
Atmospheric Pressure 86~106kPa
Brands of Main Components
Contactor Imported brand
Fuse Miro
PLC Siemens
Data processing software Kaixiang(self-developed)
Alloy Resistance Kaixiang(self-developed)

Kaixiang developed the best ultra compact and light-weight load banks. With capacities unmatched in the industry. Not only are our load banks smaller and lighter, due to our unique resistor design, they easily withstand the harsh environments that can be associated with generator testing. can custom build any unit to meet your load testing requirements.  We offer 3 phase and single phase load banks all in one package. Select your minimum step resolution, and add any customization you need.

Main features:

  • Latest in digital metering
  • Continuous duty
  • Data logging software included
  • Branch circuit fuse protection
  • High velocity cooling fans
  • Rugged construction frame
  • Over-temperature protection
  • Customized to meet your specifications
  • Weather proof enclosure
Picture of 500KW Load Bank for 3 Phase Generator Test