Customization: | Available |
---|---|
Conditions of Use: |
Land Use |
Usage: | Common Units |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC Load bank 1000kw Resistive Load Bank For Generator Testing
1) Emergency Stop: User can press the emergency stop button in the panel to unload immediately when the load bank is abnormal while working.AC415-1000kW Automatic Load Bank | |
Rating Voltage/Frequency | 415VAC, 3 phase 4 wire, wire voltage 415V, phase voltage 240V 50Hz/60hz |
Rated Load Power | Resistive load: 1000kW |
Installed Capacity | Resistive load: 1000kW |
Load Step | 1,2,2,5,10,20,20,50,100,200,200,200,200kW, min step load: 1kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | External AC400V/50Hz, 3 phase 4 wire |
Wire Connection | Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation | F |
Duty Cycle | Continuous |
Cooling Type | Force air cooling, horizontal air inlet and horizontal air outlet |
Transportation | Hoisting, there are lifting lug on top and castors at the bottom of casing |
Dimension | About 1800mm*1300mm*1918mm(L×W×H) |
Weight | About 1200kgs |
Casing Color | Grey(RAL7035)or as required |
Operating Environment Parameter | |
Workplace | Outdoor |
Ambient Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |
Brands of Main Components | |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |