System Parameter | |
Rating voltage/frequency | 380V, 3 phase 4 wire 50HZ |
Max Load Power | Apparent Power: 2625KVA Resistive Load: 2100kW Inductive Load: 1575KVAR |
Load Resolution | Resistive Load: 19steps 1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100kW,100kW,200kW,200kW,200kW, 200kW,200kW,200kW,200kW,200kW,200kW Inductive Load: 18 steps 1KVAR,2 KVAR, 2KVAR, 5KVAR, 10KVAR, 10KVAR, 20KVAR, 25KVAR,50KVAR,50KVAR, 100KVAR,100KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR,200KVAR |
Power Factor | 0.8-1 |
Load Tolerance (each step) | ±5% |
Load Tolerance (overall) | ±3% |
Fan &Control Voltage | External AC 3 phase 4 wire, 380V/50Hz |
Wire Connection | Load bank input--Copper bar (star coupling "Y") Control power input--Connector-bar |
Communication Interface | RS485,RS232 |
Insulation | F |
Max Protection Grade | IP54 |
Duty Cycle | Continuous |
Cooling | Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling |
Enclosure | Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Internal Lighting | Adequate internal lighting will be provided |
Transportation | Hoisting, there are lifting lug in top of casing |
Color | Grey RAL7035 or as required |
Dimensions | About 6058mm×2350mm×2591mm(L×W×H) |
Operating Environment Parameter | |
Workplace | Outdoor |
Ambient Temperature | -10ºC~+50ºC |
Relative Humidity | ≤95% |
Atmospheric Pressure | 86~106kPa |
Brands of Main Components | |
Contactor | Schneider |
Fuse | Miro |
PLC | Siemens |
Alloy Resistor | Kaixiang |
Data Processing Software | Kaixiang |