Max Diameter of Workpiece: | 500mm |
---|---|
Mass Scope of Workpiece: | <900kg |
Type: | Testing Electrical Equipment |
Maxcapacity: | >1000KN |
Accuracy Grade: | 0.5 |
Load Way: | Electronic Load |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Technical Parameters | |
Rating Voltage/Frequency | AC 400V/50Hz, 3 phase 4 wire |
Max Load Power | Resistive Load: 310kW |
Load Step | Resistive Load:10 steps; 1, 2, 2, 5, 10, 20, 20, 50, 100,100kW |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power Supply | Input380VAC 3 phase 4 wire 50hz |
Wire Connection | Load Power Supply Input--Copper bar (star connection) Control power supply input--Connector bar |
Communication Interface | RS485 (2), RS232 (1) |
Insulation Class | F |
Working Mode | Continuous Working |
Cooling | Forced air cooling,Horizontal inlet air,Horizontal outlet |
Transportation | Hoisting, there are lifting lug in top of case and wheel castors in bottom |
Chassis color | Black&White(RAL7035) |
Dimension | Approximately; 1250*1550*1680 (Width *Length *Height) |
Operating Environment Parameter | |
Ambient Temperature | -10ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
Suppliers with verified business licenses