Customization: | Available |
---|---|
Rated Voltage: | 415VAC 3phase 4wire 50Hz |
Rated Power: | 500kw |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Load bank testing solutions include load banks that test the operation of an electrical system. Load banks control the total load, power factor and schedule during the test. Many of the devices in an electrical system use sensors that measure current to determine their function. Electrical load needs to be added during a system test to ensure all sensors have adequate current to perform as intended.
There are three main load bank testing solutions: Resistive, Reactive and Resistive/Reactive:
Resistive Load Banks - The most common type, resistive load banks mimic the operational load that a power source will see in actual use. They convert electrical energy to heat using power resistors and dissipate the heat using air or water.
Reactive Load Banks - These solutions are used to simulate systems affected by electric motors or other electromagnetic devices on a power network. Typically, equipment that requires reactive power compensation are motor-driven devices, transformers and capacitors. Reactive Load banks can simulate either an inductive or capacitive load depending on the type of load expected on the power system
Resistive/Reactive Load Banks - These solutions combine both resistive and reactive elements in one load bank package. They may accommodate equipment up to 6250 kW. These load banks can also be used for integrated system testing of utility substation protection systems, particularly for more complex relays like distance, directional overcurrent, power directional and others.
AC415-500kW Automatic Load Bank | |
Rating Voltage/Frequency | 415VAC, 3 phase 4wire 50HZ |
Rated Load Power | 500kW |
Load Step | 1,2,2,5,10,10,20,50,100,100,200kW, min step load: 1kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Fan & Control Power | External 415VAC, 3 phase 4wire 50HZ |
Wire Connection | Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation | F |
Duty Cycle | Continuous |
Cooling Type | Force air cooling, horizontal air inlet & air outlet, with louver and protection door |
Transportation | Hoisting, there are lifting lug on top |
Protection | IP55 |
Dimension | About 1800mm*1300*1070mm(L×W×H) |
Weight | About 700kgs |
Enclosure Color | As required |
Operating Environment Parameter | |
Workplace | Outdoor |
Ambient Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |
Brands of Main Components | |
Contactor | Imported brand |
Fuse | Miro |
PLC | Siemens |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |