Customization: | Available |
---|---|
After-sales Service: | 12 Months |
Warranty: | Forever |
Still deciding? Get samples of US$ 1/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
System Parameter | |
Rating voltage/frequency | 400V, 3 phase 4 wire 50Hz |
Max Load Power | Apparent Power: 3000KVA Resistive Load: 2400kW Inductive Load: 1800KVAR |
Load Resolution | Resistive Load: 20 steps 1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100kW,200kW,200kW,200kW, 200kW,200kW,200kW,200kW,200kW,200kW,200kW,200kW Inductive Load: 17 steps 1KVAR,2 KVAR, 2KVAR, 5KVAR, 10KVAR, 10KVAR, 20KVAR, 50KVAR, 100KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR,200KVAR,200KVAR,200KVAR |
Power Factor | 0.8(lag) |
Load Tolerance (each step) | ±5% |
Load Tolerance (overall) | ±3% |
Fan &Control Voltage | External AC 3 phase 4 line, 380V/50Hz |
Wire Connection | Load bank input--Copper bar (star coupling "Y") Control power input--Connector-bar |
Communication Interface | RS485,RS232 |
Insulation | F |
Max Protection Grade | IP54 |
Duty Cycle | Continuous |
Cooling | Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling |
Enclosure | Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Internal Lighting | Adequate internal lighting will be provided |
Transportation | Hoisting, there are lifting lug in top of casing |
Color | Grey RAL7035 or as required |
Dimensions | 6058mm*2350mm*2591mm(L×W×H) |
Operating Environment Parameter | |
Workplace | Outdoor |
Ambient Temperature | -10ºC~+50ºC |
Relative Humidity | ≤95% |
Atmospheric Pressure | 86~106kPa |