Customization: | Available |
---|---|
Frequency: | 50Hz/60Hz |
Ambient Temperature: | -10 to +50 Degree |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC400-800kW Intelligent Load Bank | |
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, wire voltage 400V, phase voltage 230V |
Rated Load Power | Resistive load: 800kW |
Installed Capacity | Resistive load: 800kW |
Load Step | 1,2,2,5,10,10,20,50,100,200,200,200kW, min step load: 1kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 400VAC/50Hz, 3 phase 4 wire, 230V 1-phase |
Wire Connection | Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation | F |
Protection Grade | IP54 |
Way of Working | Continuous Working |
Casing Dimensions and Cooling | about 2440*1440*1680mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 1500kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Operating Environment Parameter | |
Workplace | Outdoor |
Ambient Temperature | -10ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |