Customization: | Available |
---|---|
Conditions of Use: |
Land Use |
Usage: | Standby Unit |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical parameter |
|
AC400-500KVA-RL |
|
Rated voltage /Frequency |
Three-phase three-wire 400V,50Hz;Three-phase four-wire 690V,50Hz |
Apprent Power |
500KVA |
Load Distribution |
Active power:440KW,Reactive power:330Kvar |
Stepping Value |
Resistive load: 10KW Inductive load: 10Kvar |
Resistor divider file |
10-440KW adjustable. |
Reactance file |
10-330Kvar adjustable |
Power factor |
0.8 |
Load Tolerance(each step) |
±5% |
Load Tolerance(overall) |
±3% |
Display Precision |
0.5 class |
Control Power Supply |
External AC three phase connection 380V/50Hz |
Wire Connection |
Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation grade |
F class |
Duty cycle |
Continuous |
Cooling |
Forced air cooling, Horizontal inlet air, Vertical cooling |
Transportation |
Hoisting, there are lifting lug in top of casing and casters in bottom of load bank |
Dimension |
1600 mm×2400mm×2000mm |
Weight |
1500Kg |
Operating Environment Parameter |
|
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Altitude |
≤2500 meters |
Atmospheric Pressure |
86~106kPa |
Main components brand |
|
Contactor |
Schneider |
Circuit Breaker |
Siemens |
Fuse |
Delixi |
SCM |
Infineon |
Alloy Resistor |
Kaixiang |
Data Management Software |
Kaixiang |