Thank you for using AC400V-10KVAR Inductive Load Bank. The system can accurately test output power and load capacity with all kinds of generators. System consists of testing/control and load bank, mainly includes AC load bank, data capture system, auto load/unload control system, heat dissipation device, assist control and PC software. User can control load bank through local control panel, also through software.
Technical Parameters |
|
Rating Voltage/Frequency |
400VAC , 3 phase4 wire /50Hz |
Max Load Power |
Inductive Load Bank:10kvar |
Load Step |
Inductive Load Bank: 1,2,2,5kvar. |
Load Tolerance(each step) |
±5% |
Load Tolerance(overall) |
±3% |
Display precision |
Class 0.5 |
Control Power Supply |
230VAC/50Hz Auxiliary Power |
Wire Connection |
Load power supply input--Copper bar (star coupling) Control power supply input--3 core socket |
Insulation Class |
F |
Duty Cycle |
Continuous |
Cooling |
Forced air cooling, air inlet from front, air outlet from after |
Transportation |
Wheel castors at the bottom |
Enclosure color |
Grey(RAL7035) |
Size |
Approximately; 571 mm*580mm*500mm (Width *Depth*Height) |
Operating Environment Parameter |
|
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Altitude |
≤1500 meters |
Atmospheric Pressure |
86~106kPa |
Measuring Control Function
--Load testing: Can load power within rated power, Test the output capacity of the generator set.
--Local control: There is local control panel with several power steps; user can load/unload by button.
--Local meter display data: Local meter can display 3 phases voltage, current, power, so on.
--Emergency stop: User can press Emergency Stop switch in panel, when the load bank is locked in this state, it can't add any load.
--Over voltage protection: When input voltage is over the safety value, it will unload automatically and give an alarm.
--Short circuit protection: When short circuit occurs, load bank will unload automatically.
--Overheating protection: When temperature is over the safety threshold, it will unload automatically and give an alarm.
--Fan interlock protection: Load bank can't add any load before working power on.
--Protection Buttons: There are buttons for some protection, when misinformation occurs or user has special needs, user can temporarily turn off the corresponding protection function.
Why choosing us
The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
The most patent technology and scientific research awards gainer in China.
Advanced detection method and strict inspection procedure build the qualified quality.
Customized production meet the individual requirement.
Prompt delivery & excellent after sales service.
Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.