AC480/380-55kw Automatic Resistive Load Bank

Product Details
Customization: Available
Output Type: AC Three Phase
Cooling
Method:
Air Cooled
Gold Member Since 2014

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
Years of Export Experience
The export experience of the supplier is more than 10 years
Self-branded
The supplier has 5 Self-brands, check the Audit Report for more information
Exhibition Experience
The supplier had participated in offline trade shows, you can check the Audit Report for more information
to see all verified strength labels (24)
  • AC480/380-55kw Automatic Resistive Load Bank
  • AC480/380-55kw Automatic Resistive Load Bank
  • AC480/380-55kw Automatic Resistive Load Bank
  • AC480/380-55kw Automatic Resistive Load Bank
  • AC480/380-55kw Automatic Resistive Load Bank
  • AC480/380-55kw Automatic Resistive Load Bank
Find Similar Products

Basic Info.

Model NO.
AC480/380-55kW
Transport Package
Wooden Case
Specification
860mm*570mm*770mm
Trademark
Triumph Load
Origin
Hebei, China (Mainland)
HS Code
9030339000
Production Capacity
200 Set/Sets Per Year

Product Description

AC480/380-55kW Automatic Resistive Load Bank

Foreword

Thank you for using AC480/380-55kW Automatic Resistive Load Bank, the equipment used to test the output power and loading capacity of High Voltage Generator. The load bank power input adopts sectional type, with remote control, easy to operation.Load bank using energy consumption method, air forced cooling, air dispersion, so that machine noise reduces greatly.

Technical Parameters

Technical Parameters

Rating Voltage/Frequency

380\480VAC 50Hz/60Hz,3phase 4 wire

Max Load Power

Resistive Load: 55kW

Load Step

Resistive Load.9steps; 0.5,1,2,2,5,5,10,10,20KW.

Power Factor

1

Load Tolerance(each step)

±5%

Load Tolerance(overall)

±3%

Display Precision

0.5 class

Control Power Supply

External 220VAC, 3phase 4wire 50Hz,

Wire Connection

Load Power Supply Input--Copper bar (star connection)

Control power supply input--Connector bar

Communication Interface

RS232 and RS485

Insulation Class

F

Duty Cycle

Continuous  

Cooling

Forced air cooling, horizontal air inlet and air outlet

Transportation

Hoisting, there are lifting lug in top of case and wheel castors on the bottom

Chassis color

Gray(RAL7035)

Size

Approximately; 860mm*570mm*770mm

(Width *Length *Height)

Weight

Approximately 350kg

Operating Environment Parameter

Ambient Temperature

-10ºC~+50ºC 

Relative Humidity

≤95%

Altitude

2550meters

Atmospheric Pressure

75kPa


(1) Temperature detection function: The temperature of the air outlet in resistor bin can be displayed by the local temperature measurement instrument.

(2) Local meter display data: local meter can display 3 phases voltage, current, active power, frequency and so on

(3)One-key load/unload: Whether load/unload by local control panel or by PC software control, user can pre-set the power then press the master load button.

(4) Control Mode Interlock: with control mode switch, no matter chooses which mode, operation of other mode is invalid, avoid the clash.

(5) Intelligent Control: through data processing software, realize all the test functions, display, record and manage the testing data, and generate curves, graphs and tables can be printed. 

(6) Remote Control
:through the switch in the remote control box, control the load over a long distance.

(7) Control Mode: local, remote or intelligent control(software) for choosing.

(8)Load bank testing: User could load any power within rated power, can test stable state three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time of generating set.

(9) Auxiliary function: The control panel is designed with a lighting switch, and a 220V power socket is reserved for computer or other temporary power consumption.

Software function

(1) Communication Mode: using photoelectric isolated RS485 communication serial port connect to PC, and with great anti-interference performance to make system control stable. Through converts like USB or RS232 realize communication protocol conversion.

(2) Load Mode: manual load or automatic load

(3) Manual Load: input power and power factor, and load according to the preset value.

(4) Automatic Load: set several load stages and duration, then complete the process according this stages automatically. 0%- 25%,- 50%,- 75%, -100%

(5) Real-time Monitor: through software display main parameter value, such as voltage, current, power, power factor, frequency and time.

(6) Security monitoring and control: monitor working state of the load bank by watching software light, when abnormally stop and protect, it can show the reason.

(7) Data Collection Interval: the minimum data resolving time is 2s.

(8) Data save and query: all the test data is saved in the software, easy to query in the history testing data.

(9) Graphical display: show real-time or history testing data, and support to print curve and graph as follows:

1) Graphs of real-time voltage, current, frequency and power; 2) Voltage graph

3) Current graph; 4) Power graph; 5) Frequency graph; 6) Power factor graph

(10) Data format: all the curves and graphs can be outputted as"JPG"format, testing data can be outputted as "Excel" format, and can be printed.

 Protection Function

(1) Short Circuit Protection: when short circuit, fuses in the load bank can insure to unload automatically.

(2)Overvoltage protection: When input voltage is over the safety value, it will unload automatically and give an alarm.

(3) Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.

(4) Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.

(5) Fan Delivery Protection: insufficient air volume with any fan, system unload automatically and give an alarm.

(6) Overload Protection With Fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.

(7) Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.

(8)Control Room Alarm:When the remote operation or intelligence operations, if operating room door is not closed, the corresponding warning light with ring.

(9) Air Outlet Alarm:the door do not open when running, light up with ring.

(10) Maintenance Room Alarm: the door do not close when running, light up with ring.

(11) Temperature On-line Monitor: Avoid load overheat, when temperature exceed setting value, will send alarm and unload automatically.

(12)Chassis Ground Protection: in order to avoid the danger of electric shock when operating, the load bank is equipped with special ground protection terminal.

Why choosing us

The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
The most patent technology and scientific research awards gainer in China.
Advanced detection method and strict inspection procedure build the qualified quality.
Customized production meet the individual requirement.
Prompt delivery & excellent after sales service.
Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.

AC480/380-55kw Automatic Resistive Load Bank
AC480/380-55kw Automatic Resistive Load Bank
AC480/380-55kw Automatic Resistive Load Bank
AC480/380-55kw Automatic Resistive Load Bank

Contact Information

Kaixiang Electrical Technology Co., LTD.
Eric Zhang
ADD:79Wangshan Rd,Luquan District,Shijiazhuang,Hebei,050221,P.R.China
TEL:+86 311 85138355
FAX:+86 311 85138383
M.T.:+86 18937738282
Our service is beyond of products,but the feeling of customers

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier