• 11kv 3MW Load Bank for Power Plant Test
  • 11kv 3MW Load Bank for Power Plant Test
  • 11kv 3MW Load Bank for Power Plant Test
  • 11kv 3MW Load Bank for Power Plant Test

11kv 3MW Load Bank for Power Plant Test

Conditions
of Use:
Land Use
Usage: Common Units
Output Type: AC Three Phase
Cooling
Method:
Air Cooled
Installation
Method:
Fixed
Generator
Type:
Diesel Generator
Customization:
Gold Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AC11-3000KW
Voltage
11kv
Installed Capaticy
3000kw
Frequency
50Hz, 60Hz
PF
1
Color
Grey 7035
Container
20FT
Technology
Metal Alloy
Control
Local and Remote
Cooling Method
Air Cooled
Application
Generator Test
Transport Package
Container
Specification
ISO
Trademark
Triumph Load
Origin
China
HS Code
90303900
Production Capacity
500 Set Per Year

Product Description

Advantage of 11KV 3MW  MV Load Bank for Generator Testing:

The ability to test critical power systems at voltages of 1.2KV to 80kV using direct-connect, High Voltage Load Bank offers engineers flexibility, time savings, cost savings, space savings and simplicity. It mainly used to commission utility, oil & gas, and industrial power systems without the need for additional transformers and cabling.

Application of 11KV 3MW  MV Load Bank for Generator Testing

Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test
Eliminate the carbon deposition of generator
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment

Technical Parameter of 11KV 3MW  MV Load Bank for Generator Testing

 

System Parameters

Rated voltage/current

AC 3 phase 3 wire11KV/50Hz

Max load power

Resistive load:3000kW

Load steps

Resistive load(R):200kW,400kW,600kW,800kW,1000kW,5 steps total 3000kW;Realize any combination between 200kW and 3000kW, step value 200kW.

Power factor

1

Load tolerance(each step)

±5%

Load tolerance(overall)

±3%

Display precision

Class 0.5

Control Power Supply

AC400V, 3 phase 4 wire ,50Hz

Control mode

Local manual control: use control panel to control(used for maintenance)

Remote manual control: use remote controller to control.

Remote intelligent control: use data management software on PC to control.

Wiring method

Load power supply input--cooper bar(star connection)

Control power supply input--connector bar

Communication interface

RS485,RS232

Insulation class

Class F

Protection grade

 IP55 during storage state. Power bin IP21, other IP55 during operation

Duty cycle

Continuous

Cooling type

Forced air cooling, horizontal air inlet, vertical air outlet.

Enclosure structure

Container sealing, with ladder to top of enclosure, with air inlet and air outlet mesh and protection door.

Transportation

Hoisting, with lifting lugs on top and standard installation fixing hole at bottom

Internal Lighting

Adequate internal lighting

Alarm light(red)

Built in alarm light  

Enclosure color

Grey(RAL7035)

Enclosure dimension

About 6058 mmx2438 mm×2591mm(L×W×H)

Working environment parameters

Ambient Temperature

-10ºC~+50ºC

Relative Humidity

≤95%

Altitude

≤2500 meters

Atmospheric Pressure

86~106kPa