Customization: | Available |
---|---|
Conditions of Use: |
Trailer Type, Marine, Land Use |
Usage: | Standby Unit, Common Units |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Generator set intelligent testing system
Generator set intelligent testing system can test output power and load capacity exactly. Its main function is to test electricity parameter contain dynamic parameter to all kinds of generating set. It is composed of monitor and load bank. It can achieve intellectualized and achieve special test to all kind of electricity parameter of generating set automatic and form schematics, curve and monitor report cooperating with position machine. It can completely give up handcraft operating. (Intelligent control, automatism and man can be selected).It can provide scientific test measure for high-power generating set equipment.
Main feature and function
1. It can test stable state three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, run duration of generating set and so on.
2. It has harmonic analysis function and power energy accumulation function. It can analyze voltage, 2-50 times harmonic capacity of current, total harmonic capacity.
3. It has setting test, fluctuating test, transient test (load increase quick, load decrease quick) ,and can test automatic max voltage, min. voltage, max current, min. current, max frequency, min. frequency and restoring time.
4. It is of powerful voltage oscillograph and photoelectricity isolate and RS485/RS232 com communication.
5. Not only it can display all stable state parameter, but also the load increase quickly, load decrease quickly, voltage, current, frequency curve, voltage curve, current harmonic curve and harmonic content.
6. Cooperating with software, It can achieve automatic testing all electricity parameter and form all kinds of chart, curve, and test report. The content of data is very abundant; the report form is of applicability. Data and report forms can be signed and changed format according to consumer's need.
7. It is of four group load control functions. Its each group can control 25% load and combine four load forms of 25%, 50%, 75% and 100% or set oneself according to users' need.
8. It is of load control function that can achieve the function of load increasing quickly and load decreasing quickly.
9. It is of loading inductive or capacitive load.(It is designed specially according consumers' need)
10. Control function not only can be controlled automatically by PC, but also manual operated with panel hand.
11. It is configured three ways sensor interface of environment temperature, humidity and atmospheric pressure and can achieve automatically the measure of environment temperature, humidity and atmospheric pressure, display and upload(Consumer configures sensor by oneself).
12. We adopt power input mode of optimize subsection for it that can be set convenient and covered all power. (1kw-Max 120kw, 0.5Kva -50.5kvA).
13. It achieves intelligent control that can test automatic all kinds of parameter include dynamic parameters. It can provide scientific test measures for high-power generating set.
14. Cooling measures: forced air cooling.
15. Operation measure: load subsection control (single-pole double throw switch, controlled by contactor) can meet any power combination in rating power.
Rating voltage/frequency |
6.6kV, 3 phase 50Hz |
Max Load Power |
Resistive Load: 3000kW |
Load Resolution |
Resistive Load: 6steps, 500kW,500kW,500kW,500kW,500kW,500kW |
Power Factor |
1 |
Load Tolerance (each step) |
±5% |
Load Tolerance (overall) |
±3% |
Fan &Control Voltage |
External AC 3 phase 4 line, 380V/50Hz |
Wire Connection |
Load bank input--Copper bar (star coupling "Y") Control power input--Connector-bar |
Communication Interface |
RS485,RS232 |
Insulation |
F |
Max Protection Grade |
IP54 |
Duty Cycle |
Continuous |
Cooling |
Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling |
Enclosure |
Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Internal Lighting |
Adequate internal lighting will be provided |
Transportation |
Hoisting, there are lifting lug in top of casing |
Color |
Grey RAL7035 or as required |
Dimensions |
About 6058mm*2350mm*2591mm(L*W*H) |
Operating Environment Parameter |
|
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Atmospheric Pressure |
86~106kPa |