Customization: | Available |
---|---|
Rated Voltage: | 11kv |
Frequency: | 60Hz / 50 Hz |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Load Bank Parameters |
|
Rated Voltage |
11kV |
Power |
5000kVA |
Power Consist |
Resistor: 4000kW Inductive:3000kvar |
Steps |
1000KW,1000KW,1000KW,1000KW,1000KVAR,1000KVAR,1000KVA |
Accuracy |
< ±2%RD |
IP |
IP55 (storage and transport) |
Transformer Parameters |
|
Capacity |
5000kVA(2×2500kVA) |
Frequency |
60Hz/50Hz |
Transformer |
3 phase |
Cooled |
AN/AF |
Current Density |
2.5~3.6A/mm2 |
Resistor Warming |
Allow average temperature rise 80K |
Insulation Class |
F Class |
Unload Current |
≤0.7% |
Insulation |
LI75AC28/AC3 |
Excitation Regulate Voltage |
No |
Connect Tranches |
Dyn11 |
Short Impedance |
≤8% |
Loss(no load and load) |
No load loss 5000W,Load loss 20000W |
Overall Demand of Machine |
|
Capacity |
5000kVA |
Frequency |
50Hz/60Hz |
PF |
0.1~1 |
Insulation Class |
≥F class |
Cooling |
Air cooled |
Accuracy of Indicating Instrument |
Above 1.0 class |
Dimension |
12000mm×2438mm×2591mm |
Single weight |
≤23000kg |
Environment |
-20ºC~50ºC |
Working Type |
Continue work in all-weather, normal operate under the rain, snow, frog and seaside air conditions. |
External Power |
3 phase 3 wire or 3 phase 5 wire, 380VAC |