General Introduction
Triumph load can simulate the real working conditions and provides a rigorous test regime for power supplies from 1kW to 60MW. Resistive, inductive(reactive),capacitive or combined load banks can be customised for any application. They can be used for testing numerous sets in a workshop environment, or used for on-site commissioning, witness tests and proof trials.
Custom-built load banks can be supplied for most powers, voltages, frequencies and sizes. Multi-voltage load banks are also available for operation over a large voltage range. At the same time, It can operate in parallel with more than two units.
Triumph load are available in stationary type for permanent installation or portable type with fork lift pocket base, castors. Larger load banks, typically above 1200kVA, are based on an ISO container construction. Special finishes including custom paint colors and stainless steel casings can be supplied.
Main features and advantages
Power consumption components adopt special alloy resistor, high-temperature resisting, small thermal drift, safe and reliable. Running temperature is 1/3 of design temperature.
Industrial heavy duty blower, horizontal inlet, vertical exhaust, low noise.
Weather-proof structure, suitable for abominable environment.
Multiple control mode: (1)Local panel control, (2)Remote control box/cabinet(3) Intelligent control(by PC software)
Multiple protection function: overvoltage, overcurrent, overheat, low over blowing rate, blower overheat, blower phase sequence reverse protection, smoke alarm etc.
Integrated design, easy to installation.
Outdoor Stationary Load Banks
Outdoor Stationary Load Banks offer the most robust, high-capacity, outdoor designs in the industry. It is setting the standard with intelligent operating controls, safety indication layouts, adjustable load step resolution, and ease of installation. It is the perfect solution for regularly scheduled testing and commissioning of mission-critical standby emergency power systems.
System Parameter |
Rating voltage/frequency |
400VAC 3 phase 4 wire, 50Hz, phase voltage 230VAC |
Max Load Power |
Apparent Power: 1500kVA
Resistive Load: 1200kW; Inductive Load: 900kvar |
Load Resolution |
Resistive Load: 14 steps, 1, 2, 2, 5, 10, 10, 20, 50, 100, 200,200,200,200,200kW
Inductive Load: 13 steps, 1, 2, 2, 5, 10, 10, 20, 50, 100,100,200,200,200kvar |
Power Factor |
0.8 |
Load Tolerance (each step) |
±5% |
Load Tolerance(overall) |
±3% |
Fan Control Power |
380VAC 3 phase 4 wire, 50Hz, phase voltage 220VAC |
Wire Connection |
Load bank input--Copper bar (star coupling "Y")
Control power input--Connector-bar |
Communication Interface |
RS485,RS232 |
Insulation |
F |
Max Protection Grade |
IP54 |
Way of Working |
Continuous Working |
Cooling |
Forced air cooling, horizontal inlet air and exhaust cooling (sidewards cooling) |
Enclosure |
Container type with a ladder, air inlet and outlet with mesh enclosure and protection door |
Transportation |
Hoisting |
Color |
RAL7032 |
Dimensions |
About 6058mm*2438mm*2591mm(L×W×H) |
Weight |
About 9000kg |
Operating Environment Parameter |
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Atmospheric Pressure |
86~106kPa |
Brands of Main Components |
Contactor |
CHINT |
Fuse |
DELIXI |
MCU |
INFINEON |
Alloy Resistor |
(self-developing) |
Data Processing Software |
(self-developing) |