High Voltage RC Load Bank for 3350KVA Generator Testing
1. Product Introduction
High Voltage RC Load Bank for 3350KVA Generator Testing
3350KVA dry type high voltage RC load bank. The resistive power is 2000KW and the capacitive power is 1350Kvar in a single high voltage ac load bank; The System is made up of two parts of measurement and control and load, mainly including the tank dry type ac load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, remote control box and PC software and so on.
This system, which is of independent research and development of electricity load test equipment by our technology, combining dry load module with the automatic measurement and control module, can accurately detect all kinds of generator output power and load capacity, full load and overload test.The system can be used with a computer to realize the intelligent control, automatically completing the special test to all electrical parameters of generating set and generating tables, graphs, and supporting the print, comprehensively from the cumbersome manual operation to provide scientific and efficient detection means for the power generating sets.
2. High Voltage RC Load Bank for 3350KVA Generator Testing Working Environment
Altitute:≤2500m
Temperature:-10°C~50°C
Humidity:≤95%RH
Working Mode:Continuous work(>6hours continuous long-term work per day)
3. High Voltage RC Load Bank for 3350KVA Generator Testing Technical Specifications
System Parameter (one set) |
|
Rating voltage/frequency |
AC 3 phase 4 wire, 10.5KV/50Hz |
Max Load Power |
Apparent Power: 3350KVA Resistive Load: 2000KW Capacitive Load: 1350Kvar |
Load Resolution |
Resistive Load: 5 steps, 450KW, 450KW, 450KW, 450KW, 200KW; Capacitive Load: 5 steps, 50Kvar, 100Kvar, 200Kvar, 500Kvar, 500Kvar. |
Power Factor |
0.8-1 |
Load Tolerance (each step) |
±5% |
Load Tolerance (overall) |
±3% |
Fan Control Power |
AC 3 phase 4 wire, 380V/50Hz |
Wire Connection |
Load bank input--Copper bar (star coupling "Y") Control power input--Connector-bar |
Communication Interface |
RS485,RS232 |
Insulation |
F |
Max Protection Grade |
IP54 |
Way of Working |
Continuous Working |
Cooling |
Forced air cooling, horizontal inlet air, vertical exhaust cooling |
Enclosure |
Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Transportation |
Hoisting, there are lifting lug in top of casing |
Color |
RAL7032 |
Dimensions |
About 9150mm*2438mm*2591mm(L×W×H) |
Weight |
About 11000kg |
Operating Environment Parameter |
|
Ambient Temperature |
-10ºC~+50ºC |
Relative Humidity |
≤95% |
Atmospheric Pressure |
86~106kPa |
Brands of Main Components |
|
Contactor |
SUNGEO |
Fuse |
CNCTCO |
MCU |
INFINEON |
Alloy Resistor |
(self-developing) |
Data Processing Software |
(self-developing) |